Section 4: Operation
January 2015
Operation
4.2.3 Data entry examples
Press the DOWN arrow key twice to access the menu structures shown in Figure 4-2 and
Figure 4-3. Use the arrow keys to navigate to the desired parameters to review/change.
Parameter values are classified as table values or select values. Table values are available from a
predefined list. For parameters such as line size or flow units. Select values are integers. floating
point numbers, or character strings and are entered one character at a time using the arrow
keys for parameters such as PV URV and calibration number.
Table value example
Setting the sensor size:
1. Press the DOWN arrow key twice to access the menu. See Figure 4-2.
2. Using the arrow keys, select line size from the basic setup menu.
3. Press the UP/DOWN arrow to increase/decrease the sensor size to the next value.
4. When you reach the desired sensor size, press “E” (the left arrow).
5. Set the loop to manual if necessary, and press “E” again.
After a moment, the LOI will display VALUE STORED SUCCESSFULLY and then display the
selected value.
Select value example
Changing the upper range limit:
1. Press the DOWN arrow key twice to access the menu. See Figure 4-2.
2. Using the arrow keys, select PV URV from the basic setup menu.
3. Press RIGHT arrow key to position the cursor.
4. Press UP or DOWN to set the number.
5. Repeat steps 3and 4 until desired number is displayed, press “E” (the left arrow).
6. Set the loop to manual if necessary, and press “E” again.
After a moment, the LOI will display VALUE STORED SUCCESSFULLY and then display the
selected value.
4.2.4 Totalizer functionality
Start totalizer
To start the totalizer, press the DOWN arrow to display the totalizer screen and press “E” to
begin totalization. A symbol will flash in the lower right hand corner indicating that the meter is
totalizing.