193
Reference Manual
00809-0100-4444, Rev AC
Appendix A: Implementing a Universal Transmitter
January 2015
Implementing a Universal Transmitter
A.10 Taylor sensors
Connect coil drive and electrode cables as shown in Figure A-19.
A.10.1 Series 1100 sensor to Rosemount 8732 transmitter
Figure A-19. Wiring Diagram for Taylor Series 1100 Sensors and Rosemount 8732
Table A-20. Taylor Series 1100 Sensor Wiring Connections
Rosemount 8732 Taylor Series 1100 sensors
1 Black
2 White
3 Green
17 S1 and S2
18 E1
19 E2
Do not connect mains or line power to the
magnetic flowtube sensor or to the transmitter
coil excitation circuit.
1
2
17
18
19
3
ROSEMOUNT 8732
TRANSMITTER
Electrode Connections
Coil Connections
TAYLOR SERIES 1100 SENSOR
C
L
A
White
Black
Green
L N G 1 2 3 4
Refer to Figure A-1 on page 174 for actual
terminal block configuration drawing.