Section 5: Advanced Configuration Functionality
January 2015
Advanced Configuration Functionality
Total control
This parameter turns the total limit HART alert ON or OFF.
ON - The transmitter will generate a HART alert when the defined conditions are met.
OFF - The transmitter will not generate a HART alert for the total limit.
Total mode
The total mode parameter sets the conditions under which the total limit HART alert will
activate. High and low limits exist for each channel and can be configured independently.
> High limit - The HART alert will activate when the totalizer value exceeds the high limit set
point.
< Low limit - The HART alert will activate when the totalizer value falls below the low limit set
point.
In range - The HART alert will activate when the totalizer value is between the high limit and low
limit set points.
Out of range - The HART alert will activate when the totalizer value exceeds the high limit set
point or falls below the low limit set point.
Total high limit
Set the net total value that corresponds to the high limit set point for the total high limit alert.
Total low limit
Set the net total value that corresponds to the low limit set point for the total low limit alert.
LOI menu path
Detailed Setup, Output Config, Totalizer, Total Limit, Total Control
Traditional fast keys
1,4,2,3,5,1
Device dashboard
2,2,4,5,4
LOI menu path
Detailed Setup, Output Config, Totalizer, Total Limit, Total Mode
Traditional fast keys
1,4,2,3,5,2
Device dashboard
2,2,4,5,3
LOI menu path
Detailed Setup, Output Config, Totalizer, Total Limit, Tot Hi Limit
Traditional fast keys
1,4,2,3,5,3
Device dashboard
2,2,4,5,1
LOI menu path Detailed Setup, Output Config, Totalizer, Total Limit, Tot Low Limit
Traditional fast keys 1,4,2,3,5,4
Device dashboard
2,2,4,5,2