Section 9: Troubleshooting
January 2015
Troubleshooting
9.2 Safety information
9.3 Installation check and guide
Use this guide to check new installations of Rosemount magnetic flowmeter systems that
appear to malfunction.
9.3.1 Transmitter
Before applying power to the magnetic flowmeter system, make the following transmitter
checks:
1. Record the transmitter model number and serial number.
2. Visually inspect the transmitter for any damage including the terminal block.
3. Verify the proper wiring connections have been made for the power and outputs.
Failure to follow these troubleshotting guidelines could result in death or serious
injury.
Installation and servicing instructions should be performed by qualified personnel
only.
Do not perform any servicing other than that contained in the operating instructions.
Verify that the operating environment of the sensor and transmitter is consistent with
the appropriate hazardous area approval.
Do not connect a Rosemount 8732EM to a non-Rosemount sensor that is located in an
explosive atmosphere.
Mishandling products exposed to a hazardous substance may result in death or
serious injury.
If the product being returned was exposed to a hazardous substance as defined by
OSHA, a copy of the required Material Safety Data Sheet (MSDS) for each hazardous
substance identified must be included with the returned goods.