Section 5: Advanced Configuration Functionality
January 2015
Advanced Configuration Functionality
High limit
Set the flow rate value that corresponds to the high limit set point for the flow limit alert.
Low limit
Set the flow rate value that corresponds to the low limit set point for the flow limit alert.
Flow limit hysteresis
Set the hysteresis band for the flow limit to determine how quickly the transmitter comes out of
alert status. The hysteresis value is used for both flow limit 1 and flow limit 2. Changing this
parameter under the configuration parameters for one channel will cause it to also change in the
other channel.
Total limit
Configure the parameters that will determine the criteria for activating a HART alert if the
measured net total falls within a set of configured criteria. This functionality can be used for
operating simple batching operations or generating alerts when certain localized values are
met. This parameter can be configured as a discrete output if the transmitter was ordered with
auxiliary outputs enabled (option code AX). If a digital output is configured for total limit, the
digital output will activate when the conditions for total mode are met.
LOI menu path
Flow 1: Detailed Setup, Output Config, DI/DO Config, Flow Limit 1, High Limit 1
Flow 2: Detailed Setup, Output Config, DI/DO Config, Flow Limit 2, High Limit 2
Traditional fast keys
Flow 1: 1,4,2,3,3,3 Flow 2: 1,4,2,3,4,3
Device dashboard
Flow 1: 2,2,4,3,1 Flow 2: 2,2,4,4,1
LOI menu path Flow 1: Detailed Setup, Output Config, DI/DO Config, Flow Limit 1, Low Limit 1
Flow 2: Detailed Setup, Output Config, DI/DO Config, Flow Limit 2, Low Limit 2
Traditional fast keys Flow 1: 1,4,2,3,3,4 Flow 2: 1,4,2,3,4,4
Device dashboard Flow 1: 2,2,4,3,2 Flow 2: 2,2,4,4,2
LOI menu path
Flow 1: Detailed Setup, Output Config, DI/DO Config, Flow Limit 1, Hysteresis
Flow 2: Detailed Setup, Output Config, DI/DO Config, Flow Limit 2, Hysteresis
Traditional fast keys Flow 1: 1,4,2,3,3,5 Flow 2: 1,4,2,3,4,5
Device dashboard 2,2,4,6
LOI menu path
Detailed Setup, Output Config, Totalizer, Total Limit
Traditional fast keys
1,4,2,3,5
Device dashboard
2,2,4,5