189
Reference Manual
00809-0100-4444, Rev AC
Appendix A: Implementing a Universal Transmitter
January 2015
Implementing a Universal Transmitter
A.6.4 Foxboro Sensor to 8732 transmitter
Connect coil drive and electrode cables as shown in Figure A-15.
Figure A-15. Generic Wiring Diagram for Foxboro Sensors and Rosemount 8732
Table A-16. Foxboro Generic Sensor Wiring Connections
Rosemount 8732 Foxboro sensors
1 L1
2 L2
3 Chassis Ground
17 Any Shield
18 Black
19 White
Do not connect mains or line power to the
magnetic flowtube sensor or to the transmitter
coil excitation circuit.
1
2
17
18
19
3
Electrodes
Coils
Ground
ROSEMOUNT 8732
TRANSMITTER
FOXBORO SENSOR
L2
L1
White
Black
Any Shield
Refer to Figure A-1 on page 174 for actual
terminal block configuration drawing.