Reference Manual
00809-0100-4444, Rev AC
Section 5: Advanced Configuration Functionality
January 2015
Advanced Configuration Functionality
Section 5 Advanced Configuration
Functionality
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 87
Configure outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 87
Configure HART . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 100
Configure LOI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 104
Additional parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 106
5.1 Introduction
This section contains information for advanced configuration parameters.
The software configuration settings for the Rosemount 8732EM can be accessed through a
HART
®
-based communicator, Local Operator Interface (LOI), AMS, or through a control system.
Before operating the 8732EM in an actual installation, you should review all of the factory set
configuration data to ensure that they reflect the current application.
5.2 Configure outputs
The configure outputs functionality is used to configure advanced features that control the
analog, pulse, auxiliary, and totalizer outputs of the transmitter.
5.2.1 Analog Output
The analog output function is used to configure all of the features of the 4-20 mA output.
Upper range value
The upper range value (URV) sets the 20 mA point for the analog output. This value is typically set
to full-scale flow. The units that appear will be the same as those selected under the units
parameter. The URV may be set between –39.3ft/sto39.3ft/s (–12m/sto12m/s) or the
equivalent range based on the selected flow units. There must be at least 1 ft/s (0.3 m/s) span or
equivalent between the URV and LRV.
LOI menu path
Detailed Setup, Output Config
Traditional fast keys
1,4,2
Device dashboard
2,2,2
LOI menu path
Detailed Setup, Output Config, Analog
Traditional fast keys
1,4,2,1
Device dashboard
2,2,2,1
LOI menu path Detailed Setup, Output Config, Analog, PV URV
Traditional fast keys 1,4,2,1
Device dashboard 2,2,2,1,4