Section 3: Advanced Installation Details
January 2015
Advanced Installation Details
Internal
When the pulse switch is set to internal, the pulse loop will be powered from the transmitter.
Supply voltage from the transmitter can be up to 12 VDC. Refer to Figure 3-8 and connect the
transmitter directly to the counter. Internal pulse power can only be used with an electronic
totalizer or counter and cannot be used with an electromechanical counter.
1. Turn off the transmitter.
2. Connect - DC to terminal 3.
3. Connect + DC to terminal 4.
Figure 3-8. Connecting to an Electronic Totalizer / Counter with Internal Power Supply
Electronic
Counter
Schematic showing
FET between
terminal 3 and 4