Section 5: Advanced Configuration Functionality
January 2015
Advanced Configuration Functionality
Example
The upper range value (20mA) is 3000 gpm. To obtain the highest resolution of the pulse
output, 10,000Hz is scaled to the full scale analog reading.
Pulse mode
The pulse mode configures the frequency output of the pulse. It can be set to either 50% duty
cycle, or fixed. There are two options that pulse mode can be configured to:
Pulse Output (user defines a fixed pulse width)
Frequency Output (pulse width automatically set to 50% duty cycle)
To use pulse width settings, pulse mode must be set to pulse output.
5.2.3 Totalizer
The totalizer provides the total amount of fluid that has passed through the meter. There are
three available totalizers:
Net total - increments with forward flow and decrements with reverse flow (reverse flow
must be enabled). Can be reset to zero using the net total reset function.
Gross/forward total - will only increment with forward flow
Reverse total - will only increment with reverse flow if reverse flow is enabled
LOI menu path Detailed Setup, Output Config, Pulse, Pulse Mode
Traditional fast keys
1,4,2,2,3
Device dashboard
2,2,2,2,2