Section 5: Advanced Configuration Functionality
January 2015
Advanced Configuration Functionality
The maximum value for the totalizers is based on 4,294,967,296 (2
32
) feet or corresponding
unit equivalent. If a totalizer reaches this value, it will automatically reset to zero and then
continue counting.
The gross/forward and reverse totalizers can be reset by manually changing the line size.
Totalizer units
Totalizer units is used to configure the units in which the totalized value will be displayed. These
units are independent of the flow units. Totalizer units are updated to match the flow units
whenever the flow units are written.
Totalizer display
The totalizer screen can be configured to display the net and gross totals or the forward and
reverse totals.
Note: Gross and forward totals are the same value.
Start totalizer
Start totalizer starts the totalizer counting from its current value.
Stop totalizer
Stop totalizer interrupts the totalizer count until it is restarted again. This feature is often used
during pipe cleaning or other maintenance operations.
Reset totalizer
Reset totalizer resets the net totalizer value to zero. The totalizer must be stopped before
resetting.
LOI menu path Detailed Setup, Output Config, Totalizer, Totalizer Units
Traditional fast keys
1,4,2,5,1
Device dashboard
2,2,2,3,5
LOI menu path Detailed Setup, Output Config, Totalizer Setup, Total Display
Traditional fast keys
1,4,3,3
Device dashboard
2,2,1,5,3
LOI menu path On totalizer screen, press “E”
Traditional fast keys
1,4,2,5,5
Device dashboard
2,2,2,3,4
LOI menu path On totalizer screen, press “E”
Traditional fast keys
1,4,2,5,6
Device dashboard
2,2,2,3,4
LOI menu path On totalizer screen, press right arrow (totalizer must be stopped)
Traditional fast keys
1,4,2,5,7
Device dashboard
2,2,2,3,4