Section 5: Advanced Configuration Functionality
January 2015
Advanced Configuration Functionality
To achieve the greatest maximum frequency output, set the pulse width to the lowest value
that is consistent with the requirements of the pulse output power source, pulse driven external
totalizer, or other peripheral equipment.
Example
The maximum flow rate is 10,000 gpm. Set the pulse output scaling such that the transmitter
outputs 10,000Hz at 10,000 gpm.
Note
Changes to pulse width are only required when there is a minimum pulse width required for
external counters, relays, etc.
Example
The external counter is ranged for 350 gpm and pulse is set for one gallon. Assuming the pulse
width is 0.5 ms, the maximum frequency output is 5.833Hz.