187
Reference Manual
00809-0100-4444, Rev AC
Appendix A: Implementing a Universal Transmitter
January 2015
Implementing a Universal Transmitter
A.6.2 Series 1800 (version 2) sensor to Rosemount 8732
transmitter
Connect coil drive and electrode cables as shown in Figure A-13.
Figure A-13. Wiring Diagram for Foxboro Series 1800 (Version 2) and Rosemount 8732
Table A-14. Foxboro Series 1800 (Version 2) Sensor Wiring Connections
Rosemount 8732 Foxboro Series 1800 sensors
1 L1
2 L2
3 Chassis Ground
17 Any Shield
18 Black
19 White
Do not connect mains or line power to the
magnetic flowtube sensor or to the transmitter
coil excitation circuit.
1
2
17
18
19
3
FOXBORO SERIES
1800 SENSOR
(VERSION 2)
ROSEMOUNT
8732
TRANSMITTER
Coil Connections
Electrode
Connections
GND L2
L1
White
Black
Shield
Refer to Figure A-1 on page 174 for
actual terminal block configuration
drawing.