Section 6: Advanced Diagnostics Configuration
January 2015
Advanced Diagnostics Configuration
Flow simulation deviation
The flow simulation deviation is a measurement of the percent difference between the simulated
velocity and the actual measured velocity from the transmitter calibration verification test. This
value can be continuously monitored using continuous SMART Meter Verification.
4-20 mA expected value
The 4-20 mA expected value is the simulated analog signal used for the 4-20 mA meter
verification test. This value is compared to the actual analog signal to determine analog output
deviation. This value can be continuously monitored using continuous SMART Meter
Verification.
4-20 mA actual value
The 4-20 mA actual value is the measured analog signal used for the 4-20 mA meter verification
test. This value is compared to the simulated analog signal to determine analog output
deviation. This value can be continuously monitored using continuous SMART Meter
Verification.
LOI menu path
Manual: Diagnostics, Variables, MV Results, Manual Results, Flow Sim Dev
Continuous: Diagnostics, Advanced Diag, Meter Verify, Measurements,
Continual Meas, Flow Sim Dev
Traditional fast keys
Manual: 1,2,3,2,2,1,6
Continuous: 1, 2, 3, 2, 2, 2, 4
Device dashboard Manual: 3,4,1,5,3,3
Continuous: 3,2,4,3,3
LOI menu path
Manual: Diagnostics, Advanced Diag, 4-20 mA Verify, View Results
Continuous: Diagnostics, Advanced Diag, Meter Verify, Measurements,
Continual Meas, 4-20 mA Expect
Traditional fast keys Manual: 1,2,3,3,2
Continuous: 1,2,3,2,5,2,5
Device dashboard Manual: N/A
Continuous: 3,2,4,4,1
LOI menu path
Manual: Diagnostics, Advanced Diag, 4-20 mA Verify, View Results
Continuous: Diagnostics, Advanced Diag, Meter Verify, Measurements,
Continual Meas, 4-20 mA Actual
Traditional fast keys Manual: 1,2,3,3,2
Continuous: 1,2,3,2,5,2,6
Device dashboard Manual: N/A
Continuous: 3,2,4,4,1