209
Reference Manual
00809-0100-4444, Rev AC
Appendix B: Product Specifications
January 2015
Product Specifications
Electrical connections
Conduit entries:
1
/2-in. NPT or M20.
Terminal block screws: 6-32 (No. 6) suitable for up to 14 AWG wire.
Safety grounding screws: external stainless assembly, M5; internal 8-32 (No. 8)
Vibration rating
3G per IEC 61298
Dimensions
See Product Data Sheet.
Weight
Aluminum - approximately 7 lbs. (3.2 kg).
316 stainless steel - approximately 23 lbs. (10.5 kg).
Add 1 pound (0.5 kg) for display option code M4 or M5.
B.1.8 F0875 Low Power Software Option
Available with DC power supply (2) and intrinsically safe outputs (B) only. This software option
lowers the coil drive current from 500mA to 75mA in order to conserve power for applications
where battery packs or solar panels are the primary power source. The coils are still driven in a
continuous manner, optimizing measurement performance. Power consumption of the
transmitter is reduced to approximately 2W. Use of the analog output results in a maximum of
1W of additional power consumption under a high alarm condition (23.5mA) and 24VDC
supply. Power consumption of the output loop can be minimized by utilizing the pulse output or
pulling information off of the HART signal. Both the pulse loop and the analog loop require
external power source to be applied. Flow performance reference accuracy is 1.0% of rate.
To ensure the sensor is calibrated with a low power calibration number, Option Code D3 has
been established. This code must appear in the transmitter and sensor model number. Sample
model numbers for lower power are:
8732EMT2B1N5M4DA1DA2D3F0875
8705THA020C7M0N5B3D3