5-4
Rosemount 3095FC
AFTER INSTALLING
COMPONENTS
After removing power to the 3095FC and installing components as needed,
perform the following steps to start the 3095FC and reconfigure the data.
NOTE
Ensure all input devices, output devices, and processes remain in a safe state
upon restoring power. An unsafe state could result in property damage.
When installing equipment in a hazardous area, ensure that all components
are approved for use in such areas. Check the product labels. Change
components only in an area known to be non-hazardous. Performing these
procedures in a hazardous area could result in personal injury or property
damage.
1. Reconnect power to the 3095FC by inserting the CHG+ / CHG-
power terminal.
2. Launch Rosemount User Interface Software, log in, and connect to
the 3095FC.
3. Verify that the configuration is correct. If it is not, continue by
configuring the required items. If major portions or the entire
configuration needs to be reloaded, perform the remaining steps.
4. Select File > Download.
5. From the Open dialog box, select the backup configuration file (has
extension *.800).
6. Select the portions of the configuration to download (restore).
7. Click Download to restore the configuration.