Security Configuration The 3095FC has two types of security.
Rosemount User Interface Security - Enables access to the
Rosemount User Interface Software and what menu items the user can
access.
3095FC Security - Enables communication to the transmitter.
Rosemount User Interface Security - Menu and Log On
See Figure 3-10 on page 3-14.
Use Operator ID and Password controls who can log on to Rosemount User
Interface Software and the Access Level controls access to menus and
screens. Up to 21 different users are permitted.
1. Select Utilities > 3095FC User Interface Security.
2. Enter the 3 alphanumeric characters for each operator I.D. (login).
Each operator I.D. must be unique. The I.D.is case sensitive. The
default is LOI.
3. Assign the four numeric characters between 0000 and 9999 to define
the password for each operator I.D (login). Users can have the same
password. The default is 1000.
4. Assign an access level for each user
Level 0: only allows access to several options in the File and
Display menus, plus all options in the Help menu.
Level 1: allows access to the menu options of Level 0 and several
options in the View menu.
Level 2: allows access the menu options of all lower level options,
Collect Data, EFM reports, and Meter menu.
Level 3: allows access the menu options of all lower level options,
several options in the Device and File menu, and the
Configuration menu.
Level 4: allows access the menu options of all lower level options
and several options in the Utilities menu.
Level 5 (system administrator level: allows access to all menus
and options.
NOTE
To prevent unauthorized users from accessing the software, delete the default
factory-assigned login (username) LOI and the password 1000 after the
security parameters are established.
Ensure that someone has Level 5 Access prior to deleting LOI 1000.