Rosemount 3095FC Piping from the static and DP meter runs connect to female ¼-18 NPT
connections. The 3095FC is an upstream device, meaning that the SP line
normally connects to the high pressure side (labeled “H” on the sensor body).
Installing the Rosemount 3095FC on a Pipestand
The following steps must be taken to install the 3095FC on a 2-in. pipestand:
1. Install the pipestand using the pipestand documentation.
2. Remove the orifice/meter run from service.
3. Install the 3095FC on a pipestand using clamps or mounting
brackets.
4. Connect the impulse lines.
5. Attach the appropriate wiring (see “Wiring” on page 2-4).
6. Using the prefabricated operator interface cable, physically connect
the 3095FC to the PC running the Rosemount User Interface
Software. One end of the cable (a 9-pin, D-shell, female connector)
plugs into a serial communications port on the PC. The other end of
the cable plugs into the 3095FC.
7. Apply power to the 3095FC (see “Apply Power” on page 2-10)
8. Log into the Rosemount User Interface Software (see page “Log into
the Software” on page 2-12)
9. Establish communication between the 3095FC and PC (see
“Establishing Communication” on page 2-13).
10. Configure the 3095FC (see “Configuration” on page 3-4)
11. Calibrate the 3095FC (see “Calibrate” on page 4-1).
12. Connect the 3095FC unit to any other external communication
devices or networks.
13. Place the meter run in service and monitor with Rosemount User
Interface Software for proper operation.
Installing the 3095FC on an Orifice Plate (Direct Mount)
The following steps must be taken to install the 3095FC on an orifice plate:
1. Remove the orifice/meter run from service.
2. Install the 3095FC on the meter run using a manifold and hardware to
secure the 3095FC to the orifice flanges.
3. Attach the appropriate wiring (see “Wiring” on page 2-4).
4. Using the prefabricated operator interface cable, physically connect
the 3095FC to the PC running the Rosemount User Interface
Software. One end of the cable (a 9-pin, D-shell, female connector)
plugs into a serial communications port on the PC. The other end of
the cable plugs into the 3095FC.
5. Apply power to the 3095FC (see “Apply Power” on page 2-10)
6. Log into the Rosemount User Interface Software (see page “Log into
the Software” on page 2-12)
7. Establish communication between the 3095FC and PC (see
“Establishing Communication” on page 2-13).
8. Configure the 3095FC (see “Configuration” on page 3-4)