Emerson Process Management 3095FC Automobile Accessories User Manual


 
Reference Manual
00809-0100-4832, Rev AA
October 2004
2-14
Rosemount 3095FC
Connect
When off-line, the 3095FC menu displays Connect. To use Connect:
1. Physically connect the 3095FC (see “Installation” on page 2-2).
2. Launch and log into Rosemount User Interface Software (see
“Getting Started with the Software” on page 2-12).
3. Perform one of the following:
Select a communications port from the Device Directory and press
the <Enter> key.
Double-click on a communications port from the Device Directory.
Click the Connect button on the toolbar.
Select Device > Connect to connect to the 3095FC currently
selected in the Device Directory. If a 3095FC is not currently
selected, the error “No 3095FC is Currently Selected” appears.
Remote Hardware Connection
To connect the PC to a remote 3095FC, a serial, dial-up modem, radio,
satellite, or other communications line should be installed. This connection is
typically made through the host port on the 3095FC. Use the Connect
command to connect to a serial or dial-up modem
Disconnect from the 3095FC
Close the screen to disconnect an on-line connection. This automatically
closes the connection.
CONFIGURATION TREE When communication is established with a 3095FC or opening a
configuration file, the Configuration Tree appears on the screen. The
Configuration Tree is used to perform the following:
Add, delete, or modify communication configurations for the 3095FC
units. The communication configurations allow the Rosemount User
Interface Software to communicate to an individual 3095FC unit.
Establish Groups of 3095FC units. A 3095FC Group is typically several
units in the same geographical area or a number of units with
something else in common. Each group contains a list of all the
3095FC devices contained within that group.
Assign an address for every 3095FC within a group. Each 3095FC has
a Station Name (Tag) and unique address with which to differentiate
each device. The Address must be different from any other host system
that may access the communications link.
Setup the 3095FC Comm Ports
Use the “+” and “–” symbols to display or hide various options.
Toggle between the Online configuration screen and the Configuration
tree/device directory using Window > >select file>.