Emerson Process Management 3095FC Automobile Accessories User Manual


 
Reference Manual
00809-0100-4832, Rev AA
March 2004
Rosemount 3095FC
C-22
Table C-20. Point Type 53 – Modbus Configuration Parameters
50 R/O FLP 4 Energy Accumulated (MMBTU or GJoules) ENGACC
51 R/O FLP 4 Uncorrected Today (MCF or km
3
) UCCTDY
52 R/O FLP 4 Uncorrected Yesterday (MCF or km
3
)UCCYDY
53 R/O FLP 4 Uncorrected Month (MCF or km
3
) UCCMTH
54 R/O FLP 4 Uncorrected Previous Month (MCF or km
3
) UCCPRV
55 R/O FLP 4 Uncorrected Accumulated (MCF or km
3
) UCCACC
56 R/O UINT 8 1 Partial Recalculation Flag PACALC
Parameter
Number
Read-
Write
Data Type Length Description Abbr.
Parameter
Number
Read-
Write
Data Type Length Description Abbr.
0 R/W BIN 1 Options:
Bits 4 through 7 – Not Used
Bit 3 – Modbus Type
0 = Standard
1 = Modbus with EFM Extensions
Bit 2 – Byte Order
0 = Least Significant Byte (LSB)
1 = Most Significant Byte (MSB)
Bit 1 – Log Modbus Events
0 = Log to Event Log
1 = No Logging
Bit 0 – Modbus Type
0 = RTU
1 = ASCII
OPTIONS
1 R/O UINT 8 1 Status STATUS
2 R/W INT 16 2 High Integer Scale HIGHINT
3 R/W INT 16 2 Low Integer Scale LOINT
4 R/W FLP 4 High Float Scale #1 HFLT1
5 R/W FLP 4 Low Float Scale #1 LFLT1
6 R/W FLP 4 High Float Scale #2 HFLT2
7 R/W FLP 4 Low Float Scale #2 LFLT2
8 R/W FLP 4 High Float Scale #3 HFLT3
9 R/W FLP 4 Low Float Scale #3 LFLT3
10 R/W FLP 4 High Float Scale #4 HFLT4
11 R/W FLP 4 Low Float Scale #4 LFLT4
12 R/W FLP 4 High Float Scale #5 HFLT5
13 R/W FLP 4 Low Float Scale #5 LFLT5
14 R/W FLP 4 High Float Scale #6 HFLT6
15 R/W FLP 4 Low Float Scale #6 LFLT6
16 R/W FLP 4 High Float Scale #7 HFLT7
17 R/W FLP 4 Low Float Scale #7 LFLT7
18 R/W FLP 4 High Float Scale #8 HFLT8
19 R/W FLP 4 Low Float Scale #8 LFLT8