Emerson Process Management 3095FC Automobile Accessories User Manual


 
Reference Manual
00809-0100-4832, Rev AA
October 2004
Rosemount 3095FC
3-30
NOTE
Normal recalculation periods are established in Meter Set-up screen using
Integral Multiplier period or the Base Multiplier Period. Upon forcing a
recalculation, the accumulations are zeroed and the flow value is logged as a
new entry. The Force Recalculation parameter is automatically set to Clear
after the recalculation.
Figure 3-22. Meter Setup
Advanced Tab Screen
Instrument Calibration Tab
See Figure 3-23 on page 3-30.
The 3095FC Instrument Calibration options allow setting the calibration
parameters for the Analog Inputs of the flow calculation.
1. Select Meter > Setup > Instrument Calib tab.
2. Dead Weight Calibration - If a deadweight tester is used to calibrate
the DP or the SP, select the respective Yes option. Enter the
Calibrated Grav. Accel. value.
3. Enter the User Correction Factor value that is multiplied by the base
volume flow equation, allowing the user to make any desired
adjustment to the flow. When using the default value 1, no correction
is applied.
Figure 3-23. Meter Setup
Instrument Calibration Tab
Screen