Reference Manual
00809-0100-4832, Rev AA
October 2004
4-4
Rosemount 3095FC
• Press Effect is the Zero Shift adjustment value; it is used as an offset to
the calibrated EU Values to compensate for the working SP effect on a
DP transmitter that was calibrated at atmospheric pressure.
• Set EU Value is the Tester Value specified for the last calibration value
that was set. Manual EU is the Live Reading for the last calibration
value that was set.
• The Timer field shows the last inactivity count-down in seconds
(starting from 3600 seconds) that occurred during the last calibration
session. Had the countdown reached 0, time-out would have taken
place, causing the calibration mode to end.
• Mode indicates:
• 0 = Use Current Calibration
• 1 = Start Calibration
• 2 = Calibrate
• 3 = Restore Previous Calibration
• 4 = Stop Calibration.
NOTE
No event is logged for the Mode Read-Only parameter.
• Type indicates which calibration value is currently being set:
• 0 = Inactive (no value)
•1 = Zero
•2 = Span
• 3 = Midpoint 1
• 4 = Midpoint 2
• 5 = Midpoint 3
•6 = Zero Shift
Figure 4-3. AI Calibration Values
Screen