Emerson Process Management 3095FC Automobile Accessories User Manual


 
Reference Manual
00809-0100-4832, Rev AA
October 2004
Rosemount 3095FC
3-18
6. When Temp Compensation is Enabled, a temperature compensation
curve is applied to the Analog Input using the board temperature of
the 3095FC as a reference. Use this feature to improve the A/D
conversion accuracy at temperature extremes for modular Analog
Inputs only; built-in Analog Inputs already have temperature
compensation. When using this feature, be sure to perform a
calibration after it is Enabled.
7. When Clipping is Enabled, the 3095FC forces the Filtered EUs to stay
within the range defined by the cut off limits. Set the cut off limits by
using the LoLo Alarm and HiHi Alarm parameters (see “AI Alarms
Tab” on page 3-19).
8. To complete point configuration click Apply.
9. Use Device > Flags > Flash Memory Save Configuration to save the
configuration to the Flash Memory in case a Cold Start must be
performed.
Figure 3-13. AI Advanced Tab
Screen