Emerson Process Management 3095FC Automobile Accessories User Manual


 
Reference Manual
00809-0100-4832, Rev AA
March 2004
Rosemount 3095FC
C-20
32 R/W FLP 4 C
4
H
10
i-Butane IBUTAN
33 R/W FLP 4 C
5
H
12
n-Pentane NPENTA
34 R/W FLP 4 C
5
H
12
i-Pentane IPENTA
35 R/W FLP 4 C
6
H
14
n-Hexane NHEXAN
36 R/W FLP 4 C
7
H
16
n-Heptane NHEPTA
37 R/W FLP 4 C
8
H
18
n-Octane NOCTAN
38 R/W FLP 4 C
9
H
20
n-Nonane NNONAN
39 R/W FLP 4 C
10
H
22
n-Decane NDECAN
40 R/W FLP 4 O
2
Oxygen OXYGEN
41 R/W FLP 4 CO Carbon Monoxide CARBMO
42 R/W FLP 4 H
2
Hydrogen HYDROG
43 R/W FLP 4 Low hw Cutoff LOFLOW
44 R/W FLP 4 High hw Setpoint – Differential Pressure LODPSP
45 R/W FLP 4 Low hw Setpoint – Differential Pressure HIDPSP
46 R/W UINT 8 1 Enable Stacked hw – Differential Pressure STDPEN
47 R/W TLP 3 Low hw TLP – Differential Pressure LO_TYP
48 R/W TLP 3 hw TLP DP_TYP
49 R/W TLP 3 Pf TLP FP_TYP
50 R/W TLP 3 Tf TLP TP_TYP
51 R/W FLP 4 hw – Orifice Differential Pressure CURDP
52 R/W FLP 4 Pf – Flowing Pressure CURSP
53 R/W FLP 4 Tf – Flowing Temperature (degrees F or C) CURTP
54 R/O BIN 1 Alarm Code:
Bit 7 – Manual Mode
0 = No Alarm Present
1 = Alarm Present
Bit 6 – No Flow
0 = No Alarm Present
1 = Alarm Present
Bit 5 – Flow Rate Register Discrepancy
0 = No Alarm Present
1 = Alarm Present
Bit 4 – Total Counts Register Discrepancy
0 = No Alarm Present
1 = Alarm Present
Bit 3 – Not Used
Bit 2 – High Alarm
0 = No Alarm Present
1 = Alarm Present
Bit 1 – Not Used
Bit 0 – Low Alarm
0 = No Alarm Present
1 = Alarm Present
ALARM
55 R/W FLP 4 Low Alarm Flow (1000 ft
3
/day or m
3
/day) LOALM
56 R/W FLP 4 High Alarm Flow (1000 ft
3
/day or m
3
/day) HIALM
57 R/W UINT 8 1 Averaging Technique AVGTYP
58 R/W UINT 8 1 Full Recalculation Flag FUCALL
Parameter
Number
Read-
Write
Data Type Length Description Abbr.