Device Point Types The tables in the rest of this section list the parameters for each of the Point
Types.
Table C-3. Point Type 3 - Analog Input
39 R/W TLP 3 Data 39
40 R/W TLP 3 Data 40
41 R/W TLP 3 Data 41
42 R/W TLP 3 Data 42
43 R/W TLP 3 Data 43
44 R/W TLP 3 Data 44
Parameter
Number
Read-Write Data Type Length Description
Parameter
Number
Read-
Write
Data Type Length Description Abbr.
0 R/W AC 10 Point Tag Identification TAG
1 R/W AC 10 Units UNITS
2 R/W UINT 16 2 Scan Period (50 millisecond intervals) SCANPR
3 R/W UINT 16 2 Filter (50 millisecond intervals) FILTER
4 R/W INT 16 2 Adjusted A/D 0% MINRAW
5 R/W INT 16 2 Adjusted A/D 100% MAXRAW
6 R/W FLP 4 Low Reading EU MINEU
7 R/W FLP 4 High Reading EU MAXEU
8 R/W FLP 4 Low Alarm EU LOAL
9 R/W FLP 4 High Alarm EU HIAL
10 R/W FLP 4 Low Low Alarm EU LOLOAL
11 R/W FLP 4 Hi Hi Alarm EU HIHIAL
12 R/W FLP 4 Rate Alarm EU RATEAL
13 R/W FLP 4 Alarm Deadband ALDBND
14 R/W FLP 4 Filtered EUs EU
15 R/W BIN 1 Mode:
Bit 7 – Manual Mode
0 = Normal Scan
1 = Manual Scan
Bit 6 – RBX on Set
0 = Disabled
1 = Active
Bit 5 – RBX on Clear
0 = Disabled
1 = Active
Bit 4 – Alarm Enable
0 = Disabled
1 = Log Alarm
Bit 3 – Not Used
Bit 2 – Not Used
Bit 1 – Clipping
0 = Disable
1 = Clipping Enable
Bit 0 – Fault Handling
0 = Retain Last EU Value
1 = Set EU Value to Fault EU Value (Parameter 19)
BIN