Emerson Process Management 3095FC Automobile Accessories User Manual


 
Reference Manual
00809-0100-4832, Rev AA
October 2004
Rosemount 3095FC
3-4
CONFIGURATION
Setting the Clock Immediately after connecting to a 3095FC for the first time, set the
Rosemount User Interface Software Clock to ensure proper logging of history.
The internal real-time clock provides time-stamping and control of the
historical databases, Event Log, Alarm Log, Audit Log, and Contract Hour.
NOTE
The time stamp reflects the time at the end of the period. Data collected from
0800 to 0900 is thus time-stamped 0900. This is used for the logging of
history.
See Figure 3-1
1. Select Device > Clock or click the Clock icon in the toolbar.
2. The display at the bottom of the calendar is the date and time from
the PC clock. Continue with Step 5 if correct.
3. If it is not correct:
a. use the arrow buttons to select the correct Month and Year
b. click on the desired day of the month
c. click on the time field and type in the desired value (type A or P for
the AM/PM field) or use the arrows.
4. The clock can automatically compensate for daylight savings time by
enabling this feature.
5. Click Apply and click OK.
Figure 3-1. Clock Screen