General Tab
The General tab sets the basic parameters for the meter.
See Figure 3-19 on page 3-26
1. Select Meter > Setup.
2. Select the Point number to be configured. Enter the meter tag. Enter
a unique Meter Description for the meter.
3. Select the Meter Type. Orifice is the default.
4. Select the Calculation Standard and Edition.
5. Select if Alarming is enabled or disabled.
6. Enter the inside Pipe Diameter (orifice) of the pipe, The U.S. units are
inches and the Metric units are millimeters.
7. Enter the Orifice Diameter (orifice) of the orifice. The U.S. units are
inches and the Metric units are millimeters.
8. Enter the Low Flow Cutoff (orifice) when the DP value of the metering
device is less than the Low Flow Cutoff value, the calculated flow is
set equal to zero. No Flow is recorded in the Alarm Log if Alarming is
Enabled. For the Orifice AGA3 calculation method, this value is in
inH
2
O (U.S.) or kPa (Metric).
9. Enter the Integral Multiplier Period (IMP) to indicate the frequency of
calculation in minutes of the Integral Multiplier Value (IMV) to be used
in the flow equation. The Integral Value (IV) portion of the flow
equation is calculated once per second. The value must be an integer
divider of 60, such as 1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, or 60.
Figure 3-19. Meter Setup
General Tab Screen