Emerson Process Management 3095FC Automobile Accessories User Manual


 
Reference Manual
00809-0100-4832, Rev AA
March 2004
Rosemount 3095FC
C-10
Table C-9. Point Type 14 – Communication Ports
Parameter
Number
Read-
Write
Data Type Length Description Abbr.
0 R/W AC 10 Tag Identification TAG
1 R/W UINT 16 2 Baud Rate BAUD
2 R/W UINT 8 1 Stop Bits SBITS
3 R/W UINT 8 1 Data Bits DBITS
4 R/W UINT 8 1 Parity:
0 = None
1 = Odd
2 = Even
PARITY
5 R/O BIN 1 Status:
Bit 7 – User Status Bits 6 through 2 – Not Used
Bit 1 – RBX Status
0 = RBX Inactive
1 = RBX Active for this port
Bit 0 – No Port Installed
0 = Comm Board Present
1 = No Comm Cards Installed
STATUS
6 R/W BIN 1 Mode:
Bit 7 – User Flag
0 = Reset
1 = Set
Bit 6 – User Flag
0 = Reset
1 = Set
Bit 5 – Store and Forward Port
0 = Same
1 = Opposite
Bit 4 – Not Used
Bit 3 – Enable RTS / CTS
0 = Disabled
1 = Enabled
Bit 2 – Enable Extra Key-On
0 = Disabled
1 = Enabled
Bit 1 = Enable RBX
0 = RBX Disabled
1 = RBX Enabled
Bit 0 – Not Used
MODE
7 R/W UINT 8 1 Key On Delay KEY
8 R/W UINT 8 1 Key Off Delay – Turnaround TURN
9 R/W UINT 8 1 Optional Interface Board Type:
Bit 5 through 7 – Not Used
Bit 4 – Radio Logic
Bit 3 – Reserved
Bit 2 – Dial-up Modem
Bit 1 – EIA-232 (RS-232)
Bit 0 – None
RCOUNT
10 R/W UINT 16 2 Host Retry Time XKEYON
11 R/O UINT 16 2 Alarm Pointer ALMPTR
12 R/O UINT 16 2 Receive Counter Copy COPY
13 R/O UINT 16 2 Retry Counter RCNTR
14 R/W UINT 16 2 Valid Receive Counter VALRCV
15 R/O UINT 8 1 Modem Status MDMSTS
16 R/W UINT 8 1 Modem Type MDMTYP
17 R/W FLP 4 Connect Time CONNTM
18 R/W AC 40 Configuration Command CFGCMD
19 R/W AC 40 Connect Command CONNCMD