Rosemount 3095FC
Table C-17. Point Type 45 – Meter Calibration and Sampler
Table C-18. Point Type 46 – Meter Configuration Parameters
Parameter
Number
Read-
Write
Data Type Length Description Abbr.
0 R/W BIN 1 Calibration Options:
Bit 5 through 7 – Not Used
Bit 4 – Orifice Thermal Expansion Factor – 1985
Requires Parameters 11 and 12 of Point Type
46 be set.
Bit 3 – Differential Pressure Water Manometer
Calibrator, Requires Parameters 4 and 5 of
Point Type 45 and Parameters 20, 21, and 22
of Point Type 46 be set.
Bit 2 – Differential Pressure Deadweight Calibrator
Requires Parameter 3 of Point Type 45 and
Parameters 20, 21, and 22 of Point Type 46
be set.
Bit 1 – Static Pressure Deadweight Calibrator
Requires Parameter 3 of Point Type 45 and
Parameters 20, 21, and 22 of Point Type 46
be set.
Bit 0 – Mercury Manometer
Requires Parameters 1 and 2 of Point Type 45
be set.
Note: Either Bit 2 or Bit 3 can be set, but not both. If
both bits are set, Bit 3 is cleared and Bit 2 is used.
OPTION
1 R/W FLP 4 Ambient Temperature of Mercury AMBTMP
2 R/W FLP 4 Temperature of Mercury when Calibrated MTPCAL
3 R/W FLP 4 Calculated Weights Gravitational Acceleration CALWGT
4 R/W FLP 4 Water Temperature when Calibrated WTPCAL
5 R/W FLP 4 Air Temperature when Calibrating ATPCAL
6 R/W FLP 4 User Correction Factor CORFAC
7 R/W UINT 8 1 Sampler Enable SPLENA
8 R/W FLP 4 Sampler Volume Accumulation VOLACC
9 R/W FLP 4 Sampler Duration SPLDUR