8 PARAMETER FUNCTIONS
Refer to Appendix 1 for the parameter list.
This chapter describes the parameter functions of the drive unit.
The parameters are basically explained in the following format.
Example: Pr. 10, 11
Pr. 10
100
Pr. 11
9999
"voltage braking operation time"
Parameter number Parameter description
Factory setting
Initial value
"voltage braking operation speed"
Pr. Setting Range Unit Operation
10 0 to 200 r/min
At the preset speed or less, the motor is stopped by voltage
braking.
0.0 to 60.0 s
Set the voltage braking time. Setting 0 coasts the motor to a stop
at the Pr. 10 setting or less.
11
9999
The voltage braking time (0 to 3s) is adjusted automatically.
The minimum increment of the setting is 0.1 in the setting range 0.0 to 60.0, or 1 in the range 0 to 60.
The value having a 0 on the right of the decimal point can be entered as an integer.
(Example: 10.0
10)
MEMO
If any parameter cannot be set, check that:
•
The start signal (STF or STR) is not "ON".
•
The parameter write disable selection (Pr. 77) setting has not been made.
•
The PU operation mode has not been selected.
When the PU operation mode cannot be selected, check that:
•
The start signal (STF or STR) is not "ON".
•
The operation mode selection (Pr. 79) setting is not other than "0".
Contents of This Chapter
The parameters marked
BASIC
are the basic operation parameters.
Refer to: Chapter 5, 5.2.2 Confirmation of the basic operation parameters
Page
8.1 Protection and Editing of the Parameters 8-6
Pr. 77 "parameter write disable selection"
Pr. 160
"user group read selection"
Pr. 173 "user group 1 registration"
Pr. 174 "user group 1 deletion"
Pr. 175 "user group 2 registration"
Pr. 176 "user group 2 deletion"