8 PARAMETER FUNCTIONS
8-27
8
Initial value
Pr. 44 "second acceleration time" 9999
Pr. 45 "second deceleration time" 9999
Pr. 110 "third acceleration time" 9999
Pr. 111 "third deceleration time" 9999
By turning "ON"/"OFF" the contact input signals, you can change the acceleration/deceleration time
during a stop or at any point during operation. Assign the RT and X9 signals to the control circuit
contact input signals.
Refer to: 8.4 Selection of the Control Circuit Contact Input Terminal Functions
As in Pr. 7 and Pr. 8, the acceleration/deceleration time is based on the value set in Pr. 20.
Pr. Setting Range Unit Signal Used Function
Pr. 21 = 0 0.0 to 3600
Pr. 21 = 1 0.00 to 360.0
s
Turning the RT signal "ON" makes the
setting valid.
44
45
9999
RT
Even if the RT signal is turned "ON", the
setting is invalid and the
acceleration/deceleration time is as set in
Pr. 7/Pr. 8.
Pr. 21 = 0 0.0 to 3600
Pr. 21 = 1 0.00 to 360.0
s
Turning the X9 signal "ON" makes the
setting valid.
110
111
9999
X9
Even if the X9 signal is turned "ON", the
setting is invalid and the
acceleration/deceleration time is as set in
Pr. 7/Pr. 8.
Pr. 7 Pr. 44 Pr. 110
Pr. 111
Pr. 45
Pr. 8
ON
ON
ON
Time
Running speed
V
alid parameters
RT signal
X9 signal
Start signal