6. TROUBLESHOOTING
6-4
Table 6-1 (Continued)
Indication
Operation
panel
(Actual
characters
)
Parameter
unit
Protective
Function Name
Detection Level
Estimated Cause (
)
and
Corrective Action ()
(E. 0HT)
External fault
The external relay or equivalent component
connected to the terminal which had been
assigned to the OH signal operated.
Refer to: Chapter 8, 8.4 Selection of the
Control Circuit Contact Input
Terminal Functions
(E. PUE)
PU disconnection
A connection fault of the operation panel or
parameter unit occurred.
Refer to: Pr. 75 [Section 8.2]
RS-485 communication was interrupted.
The number of communication retries
exceeded the Pr. 121 setting.
Refer to: Pr. 121 [Section 8.6.2]
(E. RET)
Retry excess
The number of alarms that occurred
exceeded the retry setting.
Refer to: Pr. 67 [Section 8.6.4]
(E. OLT)
Stall stop
Refer to: Pr. 22
[Section 8.5.6]
Motor overload activated the stall prevention
function consecutively, stopping the motor.
Reduce the load.
Increase the capacities of the motor and
drive unit.
E. OLT output was selected in Pr. 156.
Refer to Pr. 156 [Section 8.5.6]
(E. LF)
Phase failure
A phase failure occurred in any of the outputs
U, V, W.
MEMO
If a phase failure occurs during motor
operation, the overcurrent protective
function may be activated.
(E. P24)
P24
The PC terminal output of the control circuit is
in a short circuit.
Check the wiring.
MEMO
A reset may not be made from the RES
terminal. Make a reset in another
method.
(E.CTE)
Panel power
supply
The power supply cable of the operation
panel or parameter unit is in a short circuit.
Check the cable wiring.
(E. OPT)
Option fault
The plug-in option fitted is other than the
specified.
Power was switched on for the R, S, T of the
drive unit with the setting of the high power
factor converter connection (Pr. 30 = 2
[Section 8.5.5]).