5-4
Block Errors Table 5-2 lists conditions reported in the BLOCK_ERR parameter.
Conditions in italics are inactive for the resource block and are given
here only for your reference.
TABLE 5-2. BLOCK_ERR Conditions.
.
Modes The resource block supports two modes of operation as defined by the
MODE_BLK parameter:
Automatic (Auto) The block is processing its normal
background memory checks.
Out of Service (O/S) The block is not processing its tasks.
When the resource block is in O/S, all blocks within the resource
(device) are forced into O/S. The BLOCK_ERR parameter shows
OUT OF SERVICE. In this mode, you can make changes to all
configurable parameters. The target mode of a block may be
restricted to one or more of the supported modes.
Condition
Number
Condition Name and Description
0 Other
1 Block Configuration Error: A feature in FEATURES_SEL is set that is not
supported by FEATURES or an execution cycle in CYCLE_SEL is set that
is not supported by CYCLE_TYPE.
2 Link Configuration Error: A link used in one of the function blocks is
improperly configured.
3 Simulate Active: The simulation jumper is in place. Simulate active is not
an indication that the I/O blocks are using simulated data.
4 Local Override
5 Device Fault State Set
6 Device Needs Maintenance Soon
7 Input failure/process variable has bad status
8 Output Failure: The output is bad based primarily upon a bad input.
9 Memory Failure: A memory failure has occurred in FLASH, RAM, or
EEROM memory.
10 Lost Static Data: Static data that are stored in nonvolatile memory
have been lost.
11 Lost NV Data: Nonvolatile data that are stored in nonvolatile memory
have been lost.
12 Readback Check Failed
13 Device Needs Maintenance Now
14 Power Up: The device was just powered-up.
15 Out of Service: The actual mode is out of service.