Rosemount Model 8800C Vortex Flowmeter with FOUNDATION
TM
Fieldbus
D-10
The ACTUAL MODE region changes to OOS.
9. Click OK to return to the DELTA V EXPLORER.
10. Right-click on the TRANSDUCER block icon to access the
CONFIGURATION PARAMETERS menu.
11. Select the parameter you wish to configure, and follow the on-line
instructions to complete the configuration.
NOTE
As you make changes to the configuration parameters, the software
warns you that the changes you made may upset the process and create
a dangerous situation in your plant (see Figure D-16). Verify that the
control loop is in manual control before proceeding.
Figure D-16. TRANSDUCER BLOCK
PROPERTIES Dialog Box.
12. Repeat Steps 4 through 8 to return the mode of the transducer
block to Auto.