Fisher 8800A Automobile Parts User Manual


 
Rosemount Model 8800C Vortex Flowmeter with FOUNDATION
Fieldbus
4-8
Block/Transducer Errors The following conditions are reported in the BLOCK_ERR and
XD_ERROR parameters. Conditions in italics are inactive for the
transducer block and are given here only for your reference.
TABLE 4-2. BLOCK_ERR Conditions.
.
TABLE 4-3. XD_ERR Conditions.
Condition
Number
Condition Name and Description
0 Other
1 Block Configuration Error
2 Link Configuration Error
3
Simulate Active
4 Local Override
5 Device Fault State Set
6 Device Needs Maintenance Soon
7 Input Failure/Process Variable Has Bad Status
8 Output Failure
9 Memory Failure
10 Lost Static Data
11 Lost NV Data
12 Readback Check Failed
13 Device Needs Maintenance Now
14 Power Up: The device was just powered-up.
Condition
Number
Condition Name and Description
15 Out of Service: The actual mode is out of service.
16 Unspecified error: An unidentified error occurred.
17 General Error: A general error that cannot be specified below occurred.
18 Calibration Error: An error occurred during calibration of the device, or a
calibration error was detected during normal operations.
19 Configuration Error: An error occurred during configuration of the
device, or a configuration error was detected during normal operations.
20 Electronics Failure: An electrical component failed.
21 Mechanical Failure: A mechanical component failed.
22 I/O Failure: An I/O failure occurred.
23 Data Integrity Error: Data stored in the device are no longer valid due to
a nonvolatile memory checksum failure, a data verify after write failure,
etc.
24 Software Error: The software has detected an error due to an improper
interrupt service routine, an arithmetic overflow, a watchdog time-out, etc.
25 Algorithm Error: The algorithm used in the transducer block produced an
error due to overflow, data reasonableness failure, etc.