Rosemount Model 8800C Vortex Flowmeter with FOUNDATION
Fieldbus
2-22
Calibration Model 8800C Flowmeters are wet-calibrated at the factory and need no
further calibration during installation. The calibration factor (K-factor)
is stamped on each meter body and is entered into the electronics.
SOFTWARE
CONFIGURATION
To complete the installation of the Model 8800C Vortex Flowmeter,
configure the software to meet the requirements of your application. If
the flowmeter was pre-configured at the factory, it may be ready to
install. If not, refer to Section 3: Flowmeter Operation.
Tagging Commissioning Tag
Your Model 8800C Flowmeter has been supplied with a removable
commissioning tag that contains both the Device ID and a space to
record the device tag. The Device ID is a unique code that identifies a
particular device in the absence of a device tag. The device tag is used
as an operational identification for the device and is usually defined by
the Piping and Instrumentation Diagram (P & ID).
When commissioning more than one device on a fieldbus segment, it
can be difficult to identify which device is at a particular location. The
removable tag provided with the transmitter can aid in this process by
linking the Device ID and a physical location. For each device on the
segment, the installer should note the physical location in both places
on the removable commissioning tag and tear off the bottom portion.
The bottom portion of the tags can be used for commissioning the
segment in the control system.