Honeywell 2000 Automobile Parts User Manual


 
Maintenance
Replacement Procedures
Revision 7 HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 89
7/08
Replacement Procedures
Fuse Replacement
The motor drive circuit contains two fuses. They are located on the power distribution PWA. If it becomes
necessary to replace these fuses, follow the procedure in
Table 36 and refer to Figure 36 for fuse location.
Disconnect power before opening the actuator case to replace the fuse(s). A
potentially lethal shock hazard exists inside the case if the unit is opened while
powered.
Table 36 Motor Drive Fuse Replacment Procedure
Step Action
1 Remove AC power from actuator.
2 Remove the 6 screws and the extended cover of the actuator case. See Figure 35.
3 Lay assembly down on a flat surface.
4 Remove connectors from CPU and power distribution PWA.
5 Remove power distribution PWA.
6
Locate the two fuses on the power distribution PWA. See Figure 36. Carefully remove and
replace fuse(s) with Wickmann T1 type 6A 250V, or equivalent (not available from Honeywell).
7 Reinstall power distribution PWA.
8 Reconnect connectors to CPU and power distribution PWA.
9 Install a new gasket and replace extended cover. Secure to actuator with screws.
Power
distribution
PWA
}
Relay PWA#1
}
Relay PWA#2
Relay connector #1
Relay connector #2
Relay connector #3
Relay connector #4
CPU
connections
Figure 35 Power Distribution PWA and Relay PWA Locations