Set Up and Calibration Procedures
Revision 7 HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 61
7/08
Actuator Lower
Display
Prompt
Selections or
Range of Setting
Parameter Definition/PDA HercuLink
®
Prompt
PDA users: The prompts are organized differently on your PDA’s HercuLink
®
software. Grayed prompts are under Configuration, Maintenance. Non-grayed
prompts are under Maintenance.
LD CAL NONE
INP
MTR
COUT
ALL
POS
default = NONE
RESTORE CALIBRATION TYPE— Allows you to restore a
calbration value to its factory calibration.
Input — Restores input calibration to the factory calibration
for the current configured input type.
Motor— Restores motor calibration to the factory calibration.
Output — Restores actuator output calibration to the factory
calibration for the current configured output type.
All — Restores input (for the type configured), motor and
output (for the type configured) calibration to the factory
calibration.
POS — Allows a position sensor field calibration to be stored
as a factory calibration. This is to be used when a sensor is
replaced in the field. See “Calibrate POS Output”.
LD CFG DIS
ENAB
default = DIS
RESTORE DEFAULT FACTORY CONFIGURATION
Allows you to restore the factory default configuration.
DIS — Restore disabled.
ENAB— Restore enabled.
RESTRT DIS
ENAB
default = DIS
SYSTEM RESTART— Allows you to force the system to
restart.
DIS — Restart disabled.
ENAB— Restart enabled.
Note: The
MANRST function must be set to SYST.
* Temperature units are displayed in degrees C or F, and are set by the UNITS parameter. See SET
DISPLA set up group.
Note that the upper display contains the parameter name and the lower display contains the value.
This is to allow for the display of hours: minutes: seconds.