Set Up and Calibration Procedures
Relays Set Up Group
48 HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual Revision 7
7/08
Relay Type – Upper Limit Travel with Hysteresis
Selecting relay type
ULim will cause the relay to energize when the motor position exceeds the upper limit
trip point, and can be set up as follows. Note that relay hysteresis parameter (RLY1HY) value is set to 10,
which is 10% of range. This means that when the relay is energized, due to the motor position exceeding
the upper limit value, the relay will not de-energize until the motor moves to 10% below the trip point.
Set Up Group Parameter Value
SET RELAY2 RTYP21 ULim
R21VAL 70.0
R21HL HI
RTYP22 NONE
RLY2HY 10.0
100%
0%
Closed
70%
RELAY n
Normally Open
Motor
Position
60%
100%
0%
Closed
70%
RELAY n
Normally Open
Open
Motor
Position
60%
H
y
s
t
e
r
e
s
I
s
H
y
s
t
e
r
e
s
I
s
Open
Relay Type – Motor Starts
Selecting relay type STRT will cause the relay to trip when the number of motor starts exceeds the selected
limit. The motor starts value is stored as one of the maintenance group statistics. This example sets the
motor starts limit at 200,000 for Relay 1.
Set Up Group Parameter Value
SET RELAY1 RTYP11 STRT
R11 E* X10K
R11VAL 20
R11HL HI
RTYP12 NONE
The resulting action is that Relay 1 will trip when the number of accumulated motor starts in the
maintenance group exceeds 200,000.