Set Up and Calibration Procedures
Input Set Up Group
Revision 7 HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 41
7/08
Actuator Lower
Display
Prompt
Selections or
Range of Setting
Parameter Definition/PDA HercuLink Prompt
FSFTYPL
LAST
UP
DOWN
USER
default = DOWN
FAILSAFELO TYPE—Selects the motor position you want
the actuator to go to when input signal is below the low end
range value or on loss of input signal.
NOTE: Failsafe condition occurs when the input exceeds its
low end range value by 3%, or when the input signal goes to
zero. For input types 0 to 20mA, 0 to 5 V, and 0 to 10 V
there is no failsafe condition at the zero value.
Last Position—Actuator motor remains at last position.
Up—Actuator motor moves to full scale value.
Down—Actuator motor moves to zero value.
User selected value—Actuator motor moves to a customer-
defined value.
* Allows setting of failsafelo input value.
FsFVALL *
0 to 100%
default = 0
FAILSAFELO INPUT VALUE—(FailsafeLO Type USER
only) Selects the motor position you want the actuator to go
to when input signal is below the low end range value or on
loss of input.
Range is from 0 to 100%.
CHAR
LINR
SQRT
CUST
default = LINR
INPUT CHARACTERIZATION Selects a characterization
type that causes the actuator to characterize a linear input
signal to represent a non-linear input.
Linear— Provides linear characterization of the input signal.
Square Root Provides square root characterizations of
the input signal.
Custom— Custom characterization. Selecting custom
allows you to create a twentieth order characterization of
input value (x) and associated shaft position (y).
NOTE: Selecting CUST input characterization causes the
following prompt CUSTOM to be displayed.
CUSTOM
EQUL
QUIK
USER
default = EQUL
Equal percentage – Sets the characterization as explained
in Equal Percentage Valve Characteristic on page 42.
Values are read-only.
Quick opening - Sets the characterization as explained in
Quick Opening Valve Characteristic on page 43. Values are
read-only.
User-configurable – Lets you create your own
characterization using the following Xn VAL and Yn VAL
prompts.
Xn VAL
n = 1 - 20
0 to 100 %
Input Value as a percentage of input range. Defaults are
in increments of 5%.
Yn VAL
n = 1 - 20
0 to 100 %
Shaft Position Value as a percentage of position range.
Defaults are in increments of 5%.