Set Up and Calibration Procedures
Set Up Procedure
36 HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual Revision 7
7/08
Set Up Procedure
Each of the set up groups and their functions are either pre-configured at the factory or set to their default
values. Tables 8 through 19 list and describe the options available in each set up group. The following
procedure shows you the key press sequence to access any set up group or any associated Function
parameter. Make sure lock set up group “LOCK” function is set to “NONE” or “CAL.” Also some
parameters require that you enter a security password before you access or change the parameter.
You can use this procedure to access the set up groups and select all parameters.
Table 9 Set Up Procedure Using Display and Keypad
Step Operation Press Result
1 Enter Set Up Mode
SET UP
Upper Display = SET
Lets you know you are in the set up mode and a set up group
title is being displayed in the lower display.
Lower Display = INPUT
This is the first set up group you see when you press SET UP.
2
Select any Set Up
Group
SET UP
Successive presses of the SET UP key will display the other set
up group titles as listed in
Table 8Error! Reference source not
found..
You can also use the
or keys to scroll through the set up
groups in both directions.
Stop at the set up group title that describes the group of
parameters you want to configure. Then proceed to the next
step.
3
Select a Function
Parameter
FUNCTION
Upper Display
4-20
Shows the current value or selection for the
function prompt in the selected set up group.
IN TYP
Lower Display
Shows the first function prompt within the selected
set up group.
Example display shows Input group function prompt “IN TYP”
and the selection.
4
Select other
function parameters
FUNCTION
Successive presses of the FUNCTION key will sequentially
display the other function prompts of the selected set up group.
Stop at the function prompt that you want to change, and then
proceed to the next step.