Honeywell 2000 Automobile Parts User Manual


 
Set Up and Calibration Procedures
Input Set Up Group
Revision 7 HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 39
7/08
Input Set Up Group
Table 10 lists the parameters and selections available when the SET INPUT group is selected.
On the keypad and local display:
Press the SET UP key to enter the Input Set Up group.
Press the FUNCTION key to scroll through the prompts listed in the set up group.
Press the or keys to view selections or change range settings.
Table 10 Input Set Up Group Parameters
Actuator Lower
Display
Prompt
Selections or
Range of Setting
Parameter Definition/PDA HercuLink Prompt
IN TYP
Note: If input
type from model
selection guide
is:
0/4-20mA, 0/1-
5Vdc, 0-10Vdc
4-20
0-20
1-5V
0-5V
0-10
R_SP
INPUT ACTUATION TYPE— This selection specifies the
signal type and range you are going to use for the actuator
input. Be sure that the values configured for the high and low
range, alarm setpoint, etc. are within the measuring range
for the selected signal range.
4 to 20 mA
0 to 20 mA
1 to 5 Volts dc
0 to 5 Volts dc
0 to 10 Volts dc
Remote Setpoint (via communications)
NOTE: Changing the Input Actuation Type will restore the
actuator calibration to its factory values.
IN TYP
S_90 Series 90 – 0 to 135 ohms.
Note: If input type from model selection guide is: Series 90
control
INP HI 10.0 to 100
default = 100
INPUT HIGH RANGE VALUE in % is displayed.
NOTE: When Input Type (R_SP or S_90) is selected, Input
Hi is not configurable.
INP LO 0.0 to 90.0
default = 0.0
INPUT LOW RANGE VALUE in % is displayed.
NOTE: When Input Type (R_SP or S_90) is selected, Input
Hi is not configurable.