Revision 7 HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 59
7/08
Maintenance Set Up Group
The Maintenance set up group consists of information about actuator operation accumulated through time.
This information (or maintenance statistics) can be used to evaluate actuator operation and determine
predicted or scheduled maintenance periods.
Table 22 lists the parameters and selections available for the
SET MAINTENANCE group.
Please note that maintenance statistics are written to the EEPROM every 8 hours. Therefore the statistics
are saved in the event of a power interruption.
Table 22 Maintenance Set Up Group Parameters
Actuator Lower
Display
Prompt
Selections or
Range of Setting
Parameter Definition/PDA HercuLink
®
Prompt
PDA users: The prompts are organized differently on your PDA’s HercuLink
®
software. Grayed prompts are under Configuration, Maintenance. Non-grayed
prompts are under Maintenance.
TEMP nnnn F *
ACTUATOR TEMPERATURE
Read Only. Displays the
current internal temperature of the actuator.
TEMPHI
nnnn F *
HIGH TEMPERATURE LIMIT
— Displays the high
temperature limit of the internal actuator temperature since it
was last reset.
TEMPLO nnnn F *
LOW TEMPERATURE LIMIT
— Displays the low
temperature limit of the internal actuator temperature since it
was last reset.
hh:mm:ss
ACST
ACCUMULATED STALL TIME
Displays the accumulated
stall time of the actuator motor since it was last reset.
STARTS
nnnn
ACCUMULATED MOTOR STARTS— Displays the
accumulated motor starts since it was last reset. Multiply
displayed value times 10
5
to get actual value. Range is 0 to
999,900,000.
RLnCNT
n = 1, 2, 3 or 4
nnnn RELAY CYCLE COUNTS Displays the accumulated cycle
counts of a relay since it was last reset. One relay cycle is
when a relay is energized and deenergized.
Multiply
displayed value times 10
5
to get actual value. Range is 0 to
999,900,000.
REGNn
n = 0 to 9
nnnn ACCUMULATED MOTOR STARTS— Displays the
accumulated motor starts in the 1
st
10% of motor span since
it was last reset. See
Regions of Motor Travel (page
62). Multiply displayed value
times 10
5
to get actual value. Range is 0 to 999,900,000.
TOTDEG
nnnn TOTAL DEGREES OF MOTOR TRAVEL
Displays the
total number of degrees of motor travel since it was last
reset.
Multiply displayed value times 10
5
to get actual value.
Range is 0 to 999,900,000.