Honeywell 2000 Automobile Parts User Manual


 
Set Up and Calibration Procedures
Current Out Set Up Group
Revision 7 HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 49
7/08
Current Out Set Up Group
Table 15 lists the parameters and selections available for the SET CUROUT group.
Table 15 Current Out Set Up Group Parameters
Actuator Lower
Display
Prompt
Selections or
Range of Setting
Parameter Definition/PDA HercuLink Prompt
CUROUT
Note
: If output
type from model
selection guide
is:
0/4-20mA, 0/1-
5Vdc
4 – 20
0 – 20
1 – 5V
0 – 5V
OUTPUT SIGNAL RANGE
— Selects the signal output
range.
4 to 20 mA
0 to 20 mA
1 to 5 Volts (250 ohm resistor required)
0 to 5 Volts (250 ohm resistor required)
CUROUT
Note
: If output
type from model
selection guide
is:
Slidewire
Emulation
SW E Slidewire Emulation
CUROUT
Note
: If output
type from model
selection guide
is:
None
NONE No current output configured.