Set Up and Calibration Procedures
Relays Set Up Group
Revision 7 HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 47
7/08
Relay Type - Deviation
Setting up a relay to alarm (energize) when the motor position deviates 10% (+ or -) from the actuator
setpoint can be set up as follows.
Set Up Group Parameter Value
SET RELAY1 RTYP11 DEV
R11VAL 10.00
R11HL HI
RTYP12 DEV
R12VAL -10.00
R12HL LO
RLY1HY 0.0
The resulting action is shown below.
100%
0%
Closed
-10%
RELAY n
Normally Open
Closed
Open
Motor
Position
Input
50%
+10%