Lock Set Up Group
Revision 7 HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual 53
7/08
Lock Set Up Group
Table 19 lists the parameters and selections available for the SET LOCK group.
Table 19 Lock Set Up Group Parameters
Actuator Lower
Display
Prompt
Selections or
Range of Setting
Parameter Definition/PDA HercuLink
®
Prompt
LOCKID
0 to 4095
default = 0
PASSWORD LOCK
4-digit password can be selected to
provide security access to calibration information, set up
parameters and supervisory functions. Password can be a
number from 0 to 4095.
LOCK
NONE
CAL
CONF
FULL
default = NONE
LOCK OUT FEATURE
— Selects lockout security for
calibration and supervisory functions, and set up groups.
None— No lockout of any calibration or set up groups. You
select and change set up group values, and perform field
calibration.
Calibration— Lockout for calibration groups SET CALINP,
SET CALMTR, SET CALOUT and CAL POSOUT only. You
can select and change set up group values.
Configuration— Lockout for calibration groups and set up
group configuration. You can only scroll through and view
set up group values.
Full— Lockout for calibration and all set up group values.
Only SET LOCK and READ STATUS groups are accessible.
MAENAB
DIS
ENAB
default = ENAB
Manual / Auto
— Allows the ability to lockout mode changes
from the front panel.
Disabled
— Disables the front panel auto / manual switch
functionality.
Enabled— Enables the front panel auto / manual switch
functionality.