JKSSS+ Series 2.3 - 4.2KV
SP.7CustomAccelerationCurve(SetpointPage7)
(SecurityLevel:3)
SP7.1 Setpoint Page 7 allows the user to custom design
the acceleration curve (start curve) to the specic
application. The user can custom design up to
three different curves in the soft starter. Only one
curve can be active (enabled) at a time. Each of
the three curves has eight voltage levels, with
corresponding ramp times and a current limit
setting.
Note: Each successive voltage level must be
programmed to a voltage level equal to or greater
than the previous level. All eight levels of voltages
must be programmed and the eighth level has
been preset at 100%.
 If Custom Accel Curve has been set to curve A, B
or C on this page, the soft starter will override the
Start Control Mode selected in Setpoint Page 2,
(even if Start Control Mode in Setpoint Page 2 has
not been set to Custom Accel Curve).
Note:Setpoint Page 7 has a security level 3
requirement.
CURVE C VOLTAGE
LEVEL 6: 67%
CURVE C VOLTAGE
LEVEL 7: 82%
CURVE C RAMP
TIME 7: 2 SEC.
CURVE C VOLTAGE
LEVEL 8: 100%
CURVE C RAMP
TIME 6: 2 SEC.
CURVE C CURRENT
LIMIT: 350% FLA
CURVE C RAMP
TIME 8: 2 SEC.
Range: 0 - 100%
Increments of 1
Range: 1 - 60 SEC
Increments of 1
Range: 0 - 100%
Increments of 1
Range: 1 - 60 SEC
Increments of 1
Range: 0 - 100%
Increments of 1
Range: 1 - 60 SEC
Increments of 1
Range: 200 - 600%
Increments of 10
CUSTOM CURVE C