JKSSS+ Series - 59
JKSSS+ Series 2.3 - 4.2KV
SP.7CustomAccelerationCurve(SetpointPage7)
(SecurityLevel:3)
MENU
PAGE 7 CUSTOM
ACCELERATION CURVE
CUSTOM ACCEL CURVE
: DISABLED
Range: DISABLED,
CURVE A, B or C
(Hit DOWN ARROW six times)
CURVE A VOLTAGE
LEVEL 1: 25%
CUSTOM CURVE A
CURVE A RAMP
TIME 1: 2 SEC
CURVE A RAMP
TIME 2: 2 SEC.
CURVE A VOLTAGE
LEVEL 3: 37%
CURVE A RAMP
TIME 3: 2 SEC.
CURVE A VOLTAGE
LEVEL 2: 30%
CURVE A VOLTAGE
LEVEL 4: 45%
CURVE A VOLTAGE
LEVEL 5: 55%
CURVE A RAMP
TIME 5: 2 SEC.
CURVE A VOLTAGE
LEVEL 6: 67%
CURVE A RAMP
TIME 4: 2 SEC.
CURVE A VOLTAGE
LEVEL 7: 82%
CURVE A RAMP
TIME 7: 2 SEC.
CURVE A RAMP
TIME 6: 2 SEC.
Range: 0 - 100%
Increments of 1
Range: 1 - 60 SEC
Increments of 1
Range: 0 - 100%
Increments of 1
Range: 1 - 60 SEC
Increments of 1
Range: 0 - 100%
Increments of 1
Range: 1 - 60 SEC
Increments of 1
Range: 0 - 100%
Increments of 1
Range: 1 - 60 SEC
Increments of 1
Range: 0 - 100%
Increments of 1
Range: 1 - 60 SEC
Increments of 1
Range: 0 - 100%
Increments of 1
Range: 1 - 60 SEC
Increments of 1
Range: 0 - 100%
Increments of 1
Range: 1 - 60 SEC
Increments of 1
SP7.1 Setpoint Page 7 allows the user to custom design
the acceleration curve (start curve) to the specic
application. The user can custom design up to
three different curves in the soft starter. Only one
curve can be active (enabled) at a time. Each of
the three curves allow for eight voltage plotting
points, with corresponding ramp times and a
current limit setting.
Note: Each successive voltage level must be
programmed to a voltage level equal to or greater
than the previous level. All eight levels of voltages
must be programmed and the eighth level has
been preset at 100%.
If Custom Accel Curve has been set to curve A,
B or C on this page, the soft starter will override
the Start Control Mode selected in Setpoint Page
2, (even if Start Control Mode in Setpoint Page 2
has not been set to Custom Accel Curve).
Note:Setpoint Page 7 has a security level 3
requirement.