JKSSS+ Series - 54
JKSSS+ Series 2.3 - 4.2KV
SP.4RelayAssignment(SetpointPage4)
(SecurityLevel:2)
The protection functions are user programmable to an output relay. Factory setting for the trip functions assigned to TRIP
(AUX1) relay and alarm functions to ALARM (AUX2) relay. AUX1 - 4 are Factory Set and should not be changed.
SP4.1 The following is a list of the user programmable functions.
 
1st 2nd 3rd
OVERLOAD TRIP TRIP ONLY NONE NONE
IMBALANCE TRIP TRIP (AUX1) NONE NONE
SHORT CIRCUIT TRIP TRIP ONLY NONE NONE
OVERCURRENT TRIP TRIP (AUX1) NONE NONE
STATOR RTD TRIP NONE NONE NONE
NON-STATOR RTD TRIP NONE NONE NONE
GROUND FAULT HI SET TRIP* TRIP (AUX1) NONE NONE
GROUND FAULT LO SET TRIP* TRIP (AUX1) NONE NONE
PHASE LOSS TRIP TRIP (AUX1) NONE NONE
ACCEL TIME TRIP TRIP ONLY NONE NONE
START CURVE TRIP TRIP ONLY NONE NONE
OVER FREQUENCY TRIP NONE NONE NONE
UNDER FREQUENCY TRIP TRIP (AUX1) NONE NONE
I*I*T START CURVE TRIP (AUX1) NONE NONE
LEARNED START CURVE TRIP (AUX1) NONE NONE
PHASE REVERSAL TRIP (AUX1) NONE NONE
OVERVOLTAGE TRIP TRIP (AUX1) NONE NONE
UNDERVOLTAGE TRIP TRIP (AUX1) NONE NONE
POWER FACTOR TRIP NONE NONE NONE
TACH ACCEL TRIP NONE NONE NONE
INHIBITS TRIP TRIP (AUX1) NONE NONE
SHNT TRIP NONE NONE NONE
BYPASS DISCREPANCY NONE NONE NONE
TCB FAULT TRIP (AUX1) NONE NONE
EXTERNAL INPUT 2 NONE NONE NONE
DUAL RAMP NONE NONE NONE
THERMOSTAT TRIP (AUX1) NONE NONE
OVERLOAD WARNING ALARM (AUX2) NONE NONE
OVERCURRENT ALARM ALARM (AUX2) NONE NONE
SCR FAIL SHUNT ALARM ALARM (AUX2) NONE NONE
GROUND FAULT ALARM* ALARM (AUX2) NONE NONE
UNDERCURRENT ALARM NONE NONE NONE
MOTOR RUNNING AUX3 NONE NONE
IMBALANCE ALARM ALARM (AUX2) NONE NONE
STATOR RTD ALARM NONE NONE NONE
NON-STATOR RTD ALARM NONE NONE NONE
RTD FAILURE ALARM NONE NONE NONE
SELF TEST FAIL TRIP (AUX1) NONE NONE
THERMAL REGISTER ALARM (AUX2) NONE NONE
U/V ALARM ALARM (AUX2) NONE NONE
O/V ALARM ALARM (AUX2) NONE NONE
POWER FACTOR ALARM NONE NONE NONE
KW DEMAND ALARM NONE NONE NONE
KVA DEMAND ALARM NONE NONE NONE
KVAR DEMAND ALARM NONE NONE NONE
AMPS DEMAND ALARM NONE NONE NONE
TIMED OUTPUT NONE NONE NONE
RUN DELAY TIME NONE NONE NONE
AT SPEED AUX4 NONE NONE
*Ground fault option must be installed.