JKSSS+ Series 2.3 - 4.2KV
SP.1BasicConguration(SetpointPage1)
In Setpoint Page 1, the starter is looking for the following basic
nameplate data of the motor.
 Allows the user to enter the motor’s
FLA rating. Range of adjustment is 50 - 100% (less
programmed service factor).
: Sets the pickup point on the overload curve
as dened by the programmed motor full load current. Ex:
If the motor FLA is 100 and the service factor is 1.15, the
overload pickup point will be 115 Amps.
 Choose the motor protection overload class,
range from 5-30.
Ex: Overload Class 10 will trip in 10 seconds at six times
FLA.
  The motor design maximum allowed slip
(Select from Class A through F).
  The motor insulation temperature class
(Select A, B, C, E, F, H, K, N or S).
 Applied Voltage
  The user may choose either 50 Hz or 60
Hz.
MENU
PAGE 1 BASIC
CONFIGURATION
MOTOR FULL LOAD AMPS
: 200 AMPS
SERVICE FACTOR
: 1.15 X FLA
OVERLOAD
CLASS: 10
NEMA
DESIGN: B
INSULATION
CLASS: B
LINE VOLTAGE
INPUT: 4160 VOLTS
Range: 50 - 100% of Unit
MAX CURRENT AMPS
Increments of 1
Range: 1.00 - 1.3
Increments of 0.01
Range: 5 - 30
Increments of 5
Range: A - F
Range: A - S
Range: 100 - 7200
LINE FREQUENCY
HZ: 60
Range: 50 or 60