JKSSS+ Series - 46
JKSSS+ Series 2.3 - 4.2KV
SP.1BasicConguration(SetpointPage1)
In Setpoint Page 1, the starter is looking for the following basic
nameplate data of the motor.
Allows the user to enter the motor’s
FLA rating. Range of adjustment is 50 - 100% (less
programmed service factor).
: Sets the pickup point on the overload curve
as dened by the programmed motor full load current. Ex:
If the motor FLA is 100 and the service factor is 1.15, the
overload pickup point will be 115 Amps.
Choose the motor protection overload class,
range from 5-30.
Ex: Overload Class 10 will trip in 10 seconds at six times
FLA.
The motor design maximum allowed slip
(Select from Class A through F).
The motor insulation temperature class
(Select A, B, C, E, F, H, K, N or S).
Applied Voltage
The user may choose either 50 Hz or 60
Hz.
MENU
PAGE 1 BASIC
CONFIGURATION
MOTOR FULL LOAD AMPS
: 200 AMPS
SERVICE FACTOR
: 1.15 X FLA
OVERLOAD
CLASS: 10
NEMA
DESIGN: B
INSULATION
CLASS: B
LINE VOLTAGE
INPUT: 4160 VOLTS
Range: 50 - 100% of Unit
MAX CURRENT AMPS
Increments of 1
Range: 1.00 - 1.3
Increments of 0.01
Range: 5 - 30
Increments of 5
Range: A - F
Range: A - S
Range: 100 - 7200
LINE FREQUENCY
HZ: 60
Range: 50 or 60