Toshiba VF010H05 Remote Starter User Manual


 
JKSSS+ Series - 41
JKSSS+ Series 2.3 - 4.2KV
5.1.7CustomAccelerationCurve(SetpointPage7)
5.1.8OverloadCurveConguration(SetpointPage8)
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range Section
Custom Accel Curve Disabled Disabled, Curve A, B, or C
Custom Curve A
Curve A Voltage Level 1 25% 0-100%
Curve A Ramp Time 12 sec 1-60 sec
Curve A Voltage Level 2 30% 0-100%
Curve A Ramp Time 22 sec 1-60 sec
Curve A Voltage Level 3 37% 0-100%
Curve A Ramp Time 32 sec 1-60 sec
Curve A Voltage Level 4 45% 0-100%
Curve A Ramp Time 42 sec 1-60 sec
Curve A Voltage Level 5 55% 0-100%
Curve A Ramp Time 52 sec 1-60 sec
Curve A Voltage Level 6 67% 0-100%
Curve A Ramp Time 62 sec 1-60 sec
Curve A Voltage Level 7 82% 0-100%
Curve A Ramp Time 72 sec 1-60 sec
Curve A Voltage Level 8 100% 0-100%
Curve A Ramp Time 82 sec 1-60 sec
Curve A Current Limit 350% FLA 200-500%
Custom Curve B
Same Programmable Data Points and Ranges
as Custom Curve A
Custom Curve C
Same Programmable Data Points and Ranges
as Custom Curve A
Page 7
Custom Acceleration Curve
Level 3
Password Protection
SP7.1
Setpoint
Page
Security
Level
Description
Factory Setting
Default
Range Section
Basic Run Overload Curve
Run Curve Locked Rotor Time O/L Class 1-30 sec, O/L Class
Run Locked Rotor Current 600% FLA 400-800%
Coast Down Timer Disabled 1-60 Min, Disabled
Basic Start Overload Curve
Start Curve Locked Rotor Time O/L Class 1-30 sec, O/L Class
Start Locked Rotor Current 600% FLA 400-800%
Acceleration Time Limit 30 sec 1-300 sec, Disabled
Number of Starts Per Hour Disabled 1-6, Disabled
Time Between Starts Time 5 min1-60 Min, Disabled
Area Under Curve ProtectionDisabled Enabled or Disabled
Max I*I*T Start 368 FLA 1-2500 FLA*FLA*sec
Current Over Curve Disabled Disabled, Learn, Enabled
Learned Start Curve Bias 10% 5-40%
Time for Sampling 30 sec 1-300 sec
Level 3
Password Protection
Page 8
Overload Curve Configuration
SP8.1
SP8.2
SP8.3
SP8.4